DESIGN CRITERIA FOR A FUMIGATION FACILITY
A fumigation facility, whether a building or a chamber, must adhere
to the same basic requirements. It must be sealable, heatable, have both
circulation and exhaust capability for the air, must have a sufficiently
high stack for the exhaust and a means for distribution of the gas evenly
(likewise the Zyklon B material).
.
Execution Gas Chamber at the Mississippi State Penitentiary
Note: High exhaust stack on Death House (left)
First, if a chamber is used today, it must be a welded and pressure
tested vessel coated with an inert (epoxy) paint or stainless steel or
plastic (PVC). The doors must be gasketed with an HCN resistant material
(pickled asbestos, neoprene or Teflon®). If a building, it must be
made of brick or stone and coated both inside and out with an inert (epoxy)
paint or pitch, tar or asphalt. The doors and windows must be gasketed
or sealed with a rubberized or pitched canvas and sealed with neoprene
sealant or tar. In either case, the area must be extremely dry. The term
'sealing' has two meanings: first, to mechanically prevent leakage from
the facility; and second, to render the exposed, porous surfaces of the
facility impervious to impregnation by Zyklon B gas.
..
Gas Chamber at the Mississippi State Penitentiary
Second, the chamber or structure must have a gas generator or distribution
system for Zyklon B which would force hot air over the Zyklon B or the
generator (generator may be heated with water if sealed) and circulate
the warm air and gas. The mixture required for fumigation is 3200 parts
per million (ppm) or 0.32% total volume HCN. The chamber must be free of
obstructions and have a capability for a strong, constant and copious air
flow.
.
Controls used by United
States Gas Chambers
Third, the chamber or structure must have a means for evacuating the
poisonous air/gas mixture and replacing it with fresh air. Generally, this
is done with an exhaust or intake fan with either exhaust or intake valves
or louvered ports of sufficient size to allow reasonable air change per
hour. Usually, a sufficient cubic feet per minute (cfm) fan and intake
and exhaust aperture should permit a complete air change in 1/2 hour and
should be run for at least twice the required time of one hour, or two
hours. The larger the facility, the less practical this becomes (due to
the size of available fans) and exhaust times may take several hours or
longer.
The exhaust must be vented at a safe distance above the facility where
the air currents can dispense the gas. This is normally 40 feet above the
structure, but it should be more if the structure is sheltered from the
wind. If an incinerator is used, the stack may be only several feet in
height. It is generally too costly to incinerate the HCN because of the
air volume it must handle in a short time period.
The temperature of the walls and the air within the facility, and the
intake air, must be kept at least 10 degrees above the boiling point of
the hydrocyanic acid (78.3 degrees F) to prevent condensation of HCN on
the walls, floor and ceiling of the facility, as well as in the exhaust
system. If the temperature is below 79 degrees F and condensation occurs,
the facility must be decontaminated with chlorine bleach or ammonia, the
former being the most effective. This is accomplished by spraying the walls
either automatically or manually. If done manually, protective suits (generally
neoprene) must be worn and the technicians must utilize air breathing cylinders,
as gas masks are unsafe and dangerous. The interior of the building must
be evacuated longer to allow the chlorine bleach vapors to neutralize the
liquid HCN in the exhaust system. The interior of the building must be
washed with water and thoroughly mopped and dried before the next use.
Additionally, a check of the air inside the building must be done to
determine whether all of the HCN has been removed. The test may be either
by gas detector or by the copper acetate/benzidene test. In the former,
an electronic readout is provided with detection to 10 ppm. In the other,
a benzidene solution is mixed with a copper acetate solution and is used
to moisten a piece of test paper which turn blue in varying degrees if
HCN is present.
Continue on to Design
Criteria for an Execution Gas Chamber